Loading...
Loading...

The same transformer oil gives systematically different kV depending on the test method and electrode geometry. That is why limit tables are method-specific, and why a BDV number with no method and electrode gap cannot be interpreted.
Read the article
ppm water is ambiguous across temperature and fluid type. Relative saturation (%RS) is the unit that tracks dielectric risk — and the one that lets a mixed mineral/ester fleet be ranked on a single scale.
Read the article
Why IFT deserves routine status — and what the 2024/2025 IEC updates change for mineral oil, ester, and GTL diagnostics. A deep technical guide covering measurement methods, standards evolution, and practical maintenance implications.
Read the article
An oil sample's dissipation factor (DDF/tan δ) is measured at 90 °C on a liquid specimen; the field tan delta is measured at 20 °C on the whole installed insulation. Two specimens, two questions — and no conversion between them.
Read the article